Duct CFM to Diameter
Estimate round duct diameter from airflow (CFM) and target air velocity (FPM).
400 CFM at 900 FPM =
9.03 in round duct
Representative value from the Duct CFM to Diameter reference table.
Reference Values
Browse 36 reference values with individual detail pages for quick lookup.
Duct CFM to Diameter Calculator
Estimate a round duct diameter from airflow and target velocity.
Estimated Round Diameter
—
Reference Table
Use this complete table for quick lookup and internal linking to specific value pages.
| Airflow Scenario | Calculated Diameter | Area (ft²) | Nominal (in) |
|---|---|---|---|
| 100 CFM at 500 FPM | 6.06 in round duct | 0.2 | 6 |
| 100 CFM at 700 FPM | 5.12 in round duct | 0.143 | 5 |
| 100 CFM at 900 FPM | 4.51 in round duct | 0.111 | 5 |
| 100 CFM at 1100 FPM | 4.08 in round duct | 0.091 | 4 |
| 150 CFM at 500 FPM | 7.42 in round duct | 0.3 | 7 |
| 150 CFM at 700 FPM | 6.27 in round duct | 0.214 | 6 |
| 150 CFM at 900 FPM | 5.53 in round duct | 0.167 | 6 |
| 150 CFM at 1100 FPM | 5 in round duct | 0.136 | 5 |
| 200 CFM at 500 FPM | 8.56 in round duct | 0.4 | 9 |
| 200 CFM at 700 FPM | 7.24 in round duct | 0.286 | 7 |
| 200 CFM at 900 FPM | 6.38 in round duct | 0.222 | 6 |
| 200 CFM at 1100 FPM | 5.77 in round duct | 0.182 | 6 |
| 300 CFM at 500 FPM | 10.49 in round duct | 0.6 | 10 |
| 300 CFM at 700 FPM | 8.86 in round duct | 0.429 | 9 |
| 300 CFM at 900 FPM | 7.82 in round duct | 0.333 | 8 |
| 300 CFM at 1100 FPM | 7.07 in round duct | 0.273 | 7 |
| 400 CFM at 500 FPM | 12.11 in round duct | 0.8 | 12 |
| 400 CFM at 700 FPM | 10.24 in round duct | 0.571 | 10 |
| 400 CFM at 900 FPM | 9.03 in round duct | 0.444 | 9 |
| 400 CFM at 1100 FPM | 8.17 in round duct | 0.364 | 8 |
| 600 CFM at 500 FPM | 14.83 in round duct | 1.2 | 15 |
| 600 CFM at 700 FPM | 12.54 in round duct | 0.857 | 13 |
| 600 CFM at 900 FPM | 11.06 in round duct | 0.667 | 11 |
| 600 CFM at 1100 FPM | 10 in round duct | 0.545 | 10 |
| 800 CFM at 500 FPM | 17.13 in round duct | 1.6 | 17 |
| 800 CFM at 700 FPM | 14.48 in round duct | 1.143 | 14 |
| 800 CFM at 900 FPM | 12.77 in round duct | 0.889 | 13 |
| 800 CFM at 1100 FPM | 11.55 in round duct | 0.727 | 12 |
| 1000 CFM at 500 FPM | 19.15 in round duct | 2 | 19 |
| 1000 CFM at 700 FPM | 16.18 in round duct | 1.429 | 16 |
| 1000 CFM at 900 FPM | 14.27 in round duct | 1.111 | 14 |
| 1000 CFM at 1100 FPM | 12.91 in round duct | 0.909 | 13 |
| 1200 CFM at 500 FPM | 20.98 in round duct | 2.4 | 21 |
| 1200 CFM at 700 FPM | 17.73 in round duct | 1.714 | 18 |
| 1200 CFM at 900 FPM | 15.64 in round duct | 1.333 | 16 |
| 1200 CFM at 1100 FPM | 14.14 in round duct | 1.091 | 14 |
Frequently Asked Questions
Common questions about Duct CFM to Diameter, formulas, and typical use cases.
How is round duct diameter estimated from CFM?
The calculator first finds area from CFM/velocity, then solves the round-duct area formula for diameter.
Why does velocity affect duct size?
Higher design velocity allows smaller ducts for the same airflow, while lower velocity requires larger ducts.
What velocity should I choose?
Choose based on noise, pressure drop, and system type. Main trunks often use lower velocity than small branch runs.
Is this enough for full duct design?
Use it for quick sizing; complete designs should include friction, fittings, static pressure, and equipment constraints.
Methodology and Review
This page combines a live calculator, precomputed reference values, and FAQ content from the same conversion definition to reduce mismatch between calculator output and lookup tables.
Editorial metadata (author, reviewer, and update date) is rendered on the page and in structured data. See our editorial policy, review process, and corrections policy.
For compliance-sensitive work, verify final values against project requirements, governing standards, and manufacturer documentation.